6KBU300

—————— TECHNICAL DATA ——————

3

5

3.2.5. Dip Switches description

Denomination

Function

S1-1

Enabling of the function for quick discharge of the DC link

Standard = OFF

S1-2 ... S1-5

Selection of intervention threshold of the braking unit

Braking threshold

S1-2

S1-3

S1-4

S1-5

400V dc

OFF

OFF

OFF

ON

640V dc

OFF

OFF

ON

OFF

680V dc

OFF

ON

OFF

OFF

745V dc

ON

OFF

OFF

OFF

S1-6

Not used

S2

MASTER = Selection of braking unit function as Master (standard)

SLAVE = Selection of braking unit as Slave

S3

Button Reset of alarm condition

bu0035

3.3. SELECTION OF THE INTERVENTION THRESHOLD

The DC threshold of the braking unit must be set accordingly to the supply voltage value of the connected
inverter, setting the switches as described in the following table.

N

OTE

:

It is possible to select only one braking threshold at a time.

Voltage

Braking threshold

Position of the switches

supply

[V

BR

]

S1-2

S1-3

S1-4

S1-5

230Vac

400Vdc

OFF

OFF

OFF

ON

400Vac

680Vdc

OFF

ON

OFF

OFF

460Vac

745Vdc

ON

OFF

OFF

OFF

bu0010

3.4. PARALLEL CONNECTION OF THE UNIT

There is the possibility to connect up to four braking units in parallel. For this purpose, terminals C and D must be
parallel connected and one of the units must be set as Master function, while the others as Slave (through switch
S2).

Only the Master needs to be selected for the desired intervention threshold (through switches S1-2...S1-5).

Connect the braking units as showed in the picture, paying particular attention to the correspondance of the
terminals connection C and D. For the cascade’s command connections (terminals 5 ... 10) correspondence of
terminals polarity is not requested, but it is advisable to use twisted cables.