6KBU300

—————— STANDARD BRAKING RESISTANCES ——————

6

1

6. STANDARD BRAKING RESISTORS

In order to simplify the choice of the resistor that has to be used, here below the values of the normalized resistors
are reported, calculated on a criterion for a typical use.

P

OVL

Overload power that can be regenerated by the inverter, equal to the rated power mul-
tiplied by factor 1.36 (inverter’s overload = I

cont

x 1.36)

P

AVBR

Average power dissipated by the resistor, where the duty cycle is equal to 10%

E

B R

Maximum instantaneous energy that the resistor can dissipate

t

OVLBR

Maximum continuative braking time in overload conditions (P

OVL

)

t

B R

Maximum continuative braking time at drive rated load conditions

P

N B R

Rated continuous power of the resistor which must be equal or greater than the average
power P

AVBR

T

C

P,n

P

PBR

T

BR

n

E

BR

t

The ohmic value of the normalized resistors has been calculated in order to assure the braking current for the limit
use of 6KBU300, that is to say a 460Vac supply of the inverter (braking threshold 745Vdc).