6.2.4 Configuration parameters

The following parameters affect the operation of the Metasys N2 option card :

Operation parameter

Description

Valid input values

Default value

o27

Loss of network behavior :

0 = Immediate trip – Code ERR5

1 = ERR5 trip after timer setting o28

2 = Re-check after timer setting 028

3 = Ignore communication error

0-3

0

o28

ERR5 timer setting

(used with o27)

0.0-60.0 s

0.0 seconds

Description of Parameters o27 and o28
Parameters o27 configures how the drive reacts to a loss of network. Out of the four settings, the first (0)

setting allows for an immediate trip when a network problem occurs. The last setting (3) configures the

drive to ignore the error. The middle two settings (1 and 2) use a timer setting (o28) in conjunction with

the error setting. Parameter o28 contains the timer setting that is used when o27 is configured for a value

of 1 or 2.

6.3 Indication LED’s

The OPC-G11S-MN2 is equipped with four LED’s. The functions of the LED’s are described in Figure 1

and Table 2.

1. Power/Error

2. Not Used

3. Not Used

4. Fieldbus diagnostics