6. OPC-G11S-MN2 Overview

These sections contain all necessary information to start-up and configure the OPC-G11S-MN2.

6.1 Physical interface

Isolation: The bus is galvanically separated from the other electronics with an on board DC/DC converter. Bus

signals (N2+ and N2-) are isolated via opto-couplers.

Bus connection: The OPC-G11S-MN2 connects to the Metasys network with a 9-pin female DSUB connector or

a 6-pole terminal block. For the pin layout, refer to Table 1.

Pin

Terminal

Pin DSUB Name

Function

6

Housing

Shield

Connected to PE (Physical Earth)

-

1

Not used

-

-

2

Not used

-

-

3

Not used

-

-

4

Not used

-

2

5

Ref

Isolated GND from RS 485 side *

-

6

+5V BUS

Isolated +5V from RS 485 side *

4

7

N2-

Negative RxD/TxD according to RS 485 specification

3

8

N2+

Positive RxD/TxD according to RS 485 specification

-

9

Not Connected

-

Table 1 Pin Layout

+5V BUS and Ref are used for bus termination. Some devices, like optical transceivers (RS485 to fiber

optics) might require external power supply from these pins.