DC OEM MODULE FOR USE WITH GERAPID CIRCUIT BREAKERS

Chapter 7 Operating the Module

2011-04-26 S47183Ee rev.01

Design and specifications are subject to change without notice

17


Fig. 71-6 Secondary Disconnect with two interlocks

Fig. 71-7 Operation of Rack-in Interlock

Remote Racking

A motor drive 230V 60 Hz and 250 W (0.34 Hp) is available for
Remote Racking option. The gear-motor is installed in the
front-bottom compartment of the trolley. See Fig. 34-1.
Complete rack-in or rack-out operation lasts ~8 seconds.

Fig. 71-8 Limit switches 33-1 and 33-2.

The motor is protected by 2.5

A fuse element. Two

independent limit switches, 33-1 and 33-2, switch off the

motor drive’s supply when the trolley reaches CONNECTED
position. Limit switch 33-3 stops the trolley in TEST position.
See Fig. 71-9.

All three switches are wired to block the breaker CLOSE
operation if the trolley is between CONNECTED and TEST

positions. See circuit diagram E-2, Appendix E.

Trolley Operated Switches

Stationary part of the Module is equipped with set of trolley
position switches. See Fig. 71-9 for location.

Fig. 71-9 Position switches 33-3, S4F, 33-4, 33-5

Following signal switches are available with the Module:


Switch S4F:

NC dry contact available at (Y64

Y65).

Indicate coupling of the racking shaft with racking socket.

Switch 33-4: NO and NC dry contacts available at
(Y66 Y67) and (Y68 Y69). Indicate TEST position.

Switch 33-5: NO and NC dry contacts available at
(Y70 Y71) and (Y72 Y73). Indicate CONNECTED position.

Padlocks

There are three interlocks, which can be padlocked. Padlock’s
diameter shall not exceed 1/3 inch. Padlocks are not included.

Safety Shutters, see Fig. 33-3,

Access Console, see Fig. 71-10,

Control Compartment, see Fig. 71-10.

Fig. 71-10 Padlock set at Access Console (left) and
Control Compartment (right).

Receptacle Snap Lock

Rack-In Interlock

(release)

Rack-Out Interlock

(active)

Plug

Rack-In Interlock activated

Actuator Pins of 33-1

& 33-2

Access to 33-1 & 33-2

33-5/33-4

33-3/S4F

Racking Socket

Park position for the plug.