DC OEM MODULE FOR USE WITH GERAPID CIRCUIT BREAKERS

Chapter 7 Operating the Module

20

Design and specifications are subject to change without notice

S47183Ee rev.01 2011-04-26

1. CONNECTED position – Primary Disconnects and
Secondary Disconnect in full contact, breaker ready for normal
operation. Position Interlock, see Fig. 73-1, keeps the trolley in
this position.

2. TEST position - Primary Disconnect open and separated by
a safe distance with shutters closed. The Secondary
Disconnect is in full contact. The Trolley is withdrawn ~4 inches
and locked by Position Interlock. See Fig. 72-3.








Fig. 73-2 TEST position for remote racking trolley

3. DISCONNECTED position - Primary Disconnects open and
separated by a safe distance with shutters closed. Secondary

Disconnect is open. Trolley is withdrawn ~5 inches. See Fig. 72-
3.

4. WITHDRAWN position – Trolley outside of the module.

NOTE: Remote racking-operations require control voltage
and control commands to be provided. See Appendix E for
electrical circuit drawings.










Fig. 73-3 DISCONNECTED position for remote racking
trolley.

Remote Rack–In Procedure.

NOTE: Crank Handle is necessary for completing racking
operations. Crank Handle has to be ordered separately.

WARNING: EMERGENCY RACKING STOP circuit (Y58 Y59)
must be wired to a pushbutton (furnished by OEM). It is
recommended the STOP PB be installed on the control

compartment door. See example Fig. 73-4.
Use this pushbutton for immediate interruption of racking
operation and stop the trolley regardless of its position.






Fig. 73-4 EMERGENCY STOP pushbutton (by OEM)

Secondary Disconnect

Primary Disconnects

Position Interlock

Secondary Disconnect

Primary Disconnects

Position Interlock

EMERGENCY RACKING STOP