DC OEM MODULE FOR USE WITH GERAPID CIRCUIT BREAKERS

APPENDIX B Primary Terminals Drawings.

2011-04-26 S47183Ee rev.01

Design and specifications are subject to change without notice

29

APPENDIX C – Layout drawings





Fig. C-1 Minimum required distances for installing the DC OEM Module

TOP VIEW :

Dimension A:

-

min. 0.3 ft


Dimension B:

-

min. 7 ft

Dimension C:

-

min. 0.3 ft in case of no need for rear access,

-

min. 1.5 ft in case of need for rear access.

NOTE: Minium free space over the Module’s roof should be 1.5 ft.

Trolley