Appendix d – tightening torques tables – GE Industrial Solutions DC OEM Module For use with Gerapid DC Circuit Breaker User Manual

Page 30

Advertising
background image

DC OEM MODULE FOR USE WITH GERAPID CIRCUIT BREAKERS

APPENDIX C Layout Drawings.

30

Design and specifications are subject to change without notice

S47183Ee rev.01 2011-04-26

APPENDIX D – Tightening Torques Tables


All the tightening torques listed below are applicable for Module, Trolley and Breaker.

Table D-1 Tightening torques for mechanical construction elements

Screw size

Hex-head screws

Class 5.8

Hex-head screws

Class 8.8

Self-tapping

screws

Inch-pounds Inch-pounds

Inch-pounds

Less M3

3 – 4

5 - 6

-

M3

7 – 8

10 - 11

-

M3.5

9 - 10

15 - 17

8 - 10

M4

14 - 15

22 - 24

15 - 17

M5

26 - 29

44 - 49

62 - 68

M6

47 - 51

75 - 83

132 - 146

M8

106 - 117

177 - 194

177 - 194

M10

230 - 253

362 - 398

-

M12

362 - 398

620 - 681

-

M16

885 – 973

1500 - 1650

-

Table D-2 Tightening torques for electric circuits connections

Screw size

Auxiliary & control

circuits

Copper bus bar

connections

Inch-pounds Inch-pounds

Less M3

-

-

M3

9 - 10

-

M3.5

10 - 11

-

M4

13 - 15

-

M5

26 - 29

-

M6

52 - 58

71 - 78

M8

124 - 136

177 - 194

M10

230 - 253

354 - 390

M12

354 - 390

620 - 681

M16

531 - 584

1240 - 1360

Advertising