Feature Specifications (cont.)

Parameter

Device

Symbol

Min

Typ

Max

Units

Over Temperature Protection
(See Thermal Considerations section)

All T

ref

135 °C

PMBus Over Temperature Warning Threshold*

All

T

WARN

125 °C

Input Undervoltage Lockout

Turn-on Threshold

All

Both Inputs

4.5

Vdc

Turn-off Threshold

All

Both Inputs

4.25

Vdc

Hysteresis All

Both

Inputs

0.15 0.2

Vdc

PMBus Adjustable Input Under Voltage Lockout Thresholds

All

Both Inputs

4 14

Vdc

Resolution of Adjustable Input Under Voltage Threshold

All

Both Inputs

250

mV

PGOOD (Power Good)

Signal Interface Open Drain, V

supply

≤ 5VDC

Overvoltage threshold for PGOOD ON

All

Both Outputs

108.33

%V

O, set

Overvoltage threshold for PGOOD OFF

All

Both Outputs

112.5 %V

O, set

Undervoltage threshold for PGOOD ON

All

Both Outputs

91.67 %V

O, set

Undervoltage threshold for PGOOD OFF

All

Both Outputs

87.5 %V

O, set

Pulldown resistance of PGOOD pin

All

Both Outputs

40 70 Ω

Sink current capability into PGOOD pin

All

Both Outputs

5

mA

* Over temperature Warning – Warning may not activate before alarm and unit may shutdown before warning