Bell & Gossett IM207R00 Series 3530-F User Manual

Page 3

Advertising
background image

3

SAFETY INSTRUCTIONS

TO AVOID SERIOUS OR FATAL PERSONAL INJURY

OR MAJOR PROPERTY DAMAGE, READ AND

FOLLOW ALL SAFETY INSTRUCTIONS IN MANUAL

AND ON PUMP.
THIS MANUAL IS INTENDED TO ASSIST IN THE

INSTALLATION AND OPERATION OF THIS UNIT

AND MUST BE KEPT WITH THE PUMP.

This is a SAFETY ALERT SYMBOL.

When you see this symbol on the pump

or in the manual, look for one of the fol-

lowing signal words and be alert to the

potential for personal injury or property

damage.
Warns of hazards that WILL cause

serious personal injury, death or major

property damage.
Warns of hazards that CAN cause

serious personal injury, death or major

property damage.
Warns of hazards that CAN cause per-

sonal injury or property damage.

NOTICE: INDICATES SPECIAL INSTRUCTIONS

WHICH ARE VERY IMPORTANT AND

MUST BE FOLLOWED.

THOROUGHLY REVIEW ALL INSTRUCTIONS

AND WARNINGS PRIOR TO PERFORMING ANY

WORK ON THIS PUMP.
MAINTAIN ALL SAFETY DECALS.

UNIT NOT DESIGNED FOR USE

WITH HAZARDOUS LIQUIDS OR

FLAMMABLE GASES. THESE

FLUIDS MAY BE PRESENT IN

CONTAINMENT AREAS.

DESCRIPTION & SPECIFICATIONS:
The Models 3530 (close-coupled) and 3530-F (frame-

mounted) are end suction, single stage centrifugal pumps

for general liquid transfer service, booster applications,

etc. Liquid-end construction is all AISI Type 316 stainless

steel, stamped and welded. Impellers are fully enclosed,

non-trimable to intermediate diameters. Casings are fitted

with a diffuser for efficiency and for negligible radial shaft

loading.
Close-coupled units have NEMA 48J or 56J motors with

C-face mounting and threaded shaft extension. Frame-

mounted units can be coupled to motors through a spacer

coupling, or belt driven.

1. IMPORTANT:

1.1. Inspect unit for damage. Report any damage to car-

rier/dealer immediately.

1.2. Electrical supply must be a separate branch circuit

with fuses or circuit breakers, wire sizes, etc., per

national and local electrical codes. Install an all-leg

disconnect switch near pump.

Always disconnect electrical power when

handling pump or controls.

1.3. Motors must be wired for proper voltage. Motor wir-

ing diagram is on motor nameplate. Wire size must

limit maximum voltage drop to 10% of nameplate

voltage at motor terminals, or motor life and pump

performance will be lowered.

1.4. Always use horsepower-rated switches, contactor and

starters.

1.5. Motor Protection

1.5.1. Single-phase: Thermal protection for single-

phase units is sometimes built in (check name-

plate). If no built-in protection is provided, use

a contactor with a proper overload. Fusing is

permissible.

1.5.2. Three-phase: Provide three-leg protection with

properly sized magnetic starter and thermal

overloads.

1.6. Maximum Operating Limits:
Liquid Temperature: 212º F (100º C) with standard seal

250º F (120º C) with optional high

temp seal

Pressure:

75 PSI

Starts Per Hour:

20, evenly distributed

1.7. Regular inspection and maintenance will increase

service life. Base schedule on operating time. Refer to

Section 8.

2. INSTALLATION:

2.1. General

2.1.1. Locate pump as near liquid source as possible

(below level of liquid for automatic operation).

2.1.2. Protect from freezing or flooding.
2.1.3. Allow adequate space for servicing and ventila-

tion.

2.1.4. All piping must be supported independently of

the pump, and must “line-up” naturally.

Never draw piping into place by forcing the

pump suction and discharge connections.

2.1.5. Avoid unnecessary fittings. Select sizes to keep

friction losses to a minimum.

2.2. Close-Coupled Units

2.2.1. Units may be installed horizontally, inclined or

vertically.

Do not install with motor below pump.

Any leakage or condensation will affect

the motor.

2.2.2. Foundation must be flat and substantial to

eliminate strain when tightening bolts. Use

rubber mounts to minimize noise and vibration.

2.2.3. Tighten motor hold-down bolts before

connecting piping to pump.

2.3. Frame-Mounted Units

2.3.1. It is recommended that the bedplate be grouted

to a foundation with solid footing. Refer to

Figure 1.

DANGER

WARNING

CAUTION

WARNING

Hazardous fluids

can cause fire,

burns or death.

CAUTION

CAUTION

CAUTION