Alpha Technologies FXM 650, 1100, 2000 UPS User Manual

Page 40

Advertising
background image

017-230-B4 Rev B

38

Figure 22 — UPS Maintenance: Battery,

Standard charging method

UPS Maintenance > Battery

Setting the Battery Charging Method to Standard or Bulk in the Battery Primary Configuration table

determines which parameters can be set or adjusted. See Figure 22 and Figure 23. The Standard charging

method is the default setting.

Standard Charging Method

Standard Charger Mode

Auto

: Charger stops charging when the battery is

fully charged.

Constant

: Charger switches to float mode when the

battery becomes charged. Float voltage is 0.4V lower

than maximum charging voltage and is temperature

compensated.

Temperature Compensation

Adjustable from 0 to -6.0 in increments of 0.5.

(Factory default is -5 mV/°C/Cell)

Max Charger Current

Charging current can be set to 0 or any value

between 2A and maximum in increments of 1A

(maximum = 15A for FXM1100/FXM2000 and 10A for

FXM650). Charging current cannot be set to 1A.

When charging current is set to 0A, charger will stop

charging.

Low Battery Warning

Battery voltage value that activates the low battery

warning alarm. For the range of 24V and 48V

settings, refer to the Low Battery Warning entry in

Table I on page 65. The alarm is removed when

battery voltage is 2V above the warning setting for

a 48V battery, or 1V above the warning setting for a

24V battery.

Peukert Number

Refer to Appendix A to calculate the Peukert number.

Capacity

Rated capacity (Ah) of the battery shown on the

battery data sheet. Do not confuse the battery

capacity with the Peukert capacity.

Battery Open Circuit Voltage

Obtain this number from the battery data sheet. The

value is for a single battery, so for a 48V system with

4 batteries connected in series, multiply the number

by 4. For a 24V system with 2 batteries connected in

series, multiply by 2.

Low Voltage Disconnect

and

Low Voltage Reconnect

are available when either standard or bulk charging method

is selected.

Parameter

48V

24V

Default

Minimum Maximum

Default

Minimum

Maximum

Low Voltage Disconnect (Vdc)

42

42

45

21

21

23

Low Voltage Reconnect (Vdc)

48

48

51

24

24

26