4 specifications, 0 introduction – Alpha Technologies ACS HP Series User Manual

Page 12

Advertising
background image

12

AIP900-0012-B0-001 Rev. A (01/2012)

Specifications

Electrical

Input:

Voltage:

Nominal:

208 to 250Vac

Operating:

187 to 312Vac

Extended:

187 to 90Vac (derated)

Phase:

1 or 3

Frequency:

45 to 70Hz

Current:

23A/module-nom. (130A Max@ 175ADC output)

Power:

4400W continuous/module

Power Factor:

>0.99 (50 to 100% load)

THD:

<5%

Efficiency:

>93%

Output:

Voltage:

90 to 160Vdc

Current:

35A/module-nom. (200A Max @ 110VDC)

Load Regulation:

Static <±0.5%

Line Regulation:

Static <±0.1%

Transient Response:

<±5% for 40 to 90% load step, 30ms recovery time

Ripple:

±30mVrms Battery Eliminator

Mechanical
Dimensions:

Standard

XL

mm:

1049 H x 622 W x 597 D

1806 H x 700 W x 622 D

in:

41.25 H x 24.5 W x 23.5 D

71.1 H x 27.55 W x 24.5 D

Weight:

100 kg (220 lbs) for 105A system

115 kg (253 lbs) for 105A system

Cabinet:

NEMA 1 (black finish)

NEMA 1 (black finish)

Environmental
Temperature

Standard:

-40˚ to 50°C (-40˚ to 122°F)

Extended:

-40˚ to 75°C (-40˚ to 167°F)

Storage:

-40˚ to 85°C (-40˚ to 185°F)

Humidity:

0 to 95% RH non-condensing

Elevation:

-500 to 2,800m (-1,640 to 9,186ft);

to 4,000m (13,124ft) derated to 40˚C (104˚F)

Audible Noise:

<55dBa @ 1m (3ft)

Ventilation:

Forced Air/Convection

MTBF:

>350,000 hours

Standard Features

Full graphic touch screen LCD with virtual alphanumeric and numeric keyboards
Modbus Protocol
Access GUI user interface via Internet browser through Ethernet port or RS-232 craft

port on CXC Controller
High interrupting current input and output breakers (10kA IC)
Reverse polarity protection
AC and DC surge suppression
Current limit protection
Soft start protection
Common Form C alarm relay contacts
High voltage shutdown
AC failure alarm
High/Low voltage alarm
Charger failure alarm
Positive/Negative ground fault alarm
DC output failure alarm

Standard Features (continued)

Control Functions

Automatic, scheduled, or manual float charging (adjustable)

Automatic, scheduled, or manual equalize charging (adjustable)

High/Low voltage alarm setting (adjustable)

Charge current limit (adjustable)

Automatic or manual battery testing

Battery capacity and runtime prediction

Temperature compensation
Daily Statistics: Minimum, maximum and average on input channels,

with date and time stamp

Battery current, rectifier current, and AC mains volt-

age for prior 90 days

Event Log:

On all events such as alarms, power on, any change

of state of the digital inputs, or other miscellaneous

events

Battery Log:

Battery health history on last 20 discharges, time of

discharge, and battery capacity

Options

Low voltage disconnect
DC Output Panel
Up to 10 x 2 Pole, 5-60A breakers (10kA IC) with alarm monitoring
DNP3 Level 2

Standards, Certifications

Safety:

EN 60950
UL 60950-1 (pending)
CSAC22.2 No. 60950-1-03
CE EN 60950, CB Scheme
Telcordia (Bellcore) GR-1089-CORE

EMC:

EN 55022 (CISPR 22)

EN 61000-3-2 EN 61000-3-3

EN 61000-4-2 EN 61000-4-3

EN 61000-4-4 EN 61000-4-5

EN 61000-4-6 EN 61000-4-11

ETS 300 019-1-1 ETS 300 019-1-2

ETS 300 753 IEC60950

ICES-003 Class B FCC Part 15 Class B

FCC Part 68

1.4 Specifications

1.0 Introduction

Advertising