Preliminary, Emergency shutdown procedure – Alpha Technologies ACS HP Series User Manual

Page 21

Advertising
background image

Preliminary

21

AIP900-0012-B0-001 Rev. A (01/2012)

Emergency Shutdown Procedure

CAUTION!

WARNING!

In an emergency, Line power may be disconnected at the service entrance or main electrical panel to protect

emergency personnel, but there can still be AC power present at the UPS output. You must always turn OFF the

battery circuit breaker.

1. Turn OFF the battery Circuit Breaker of the UPS.

2. Turn OFF the Generator (if connected).

3. Turn OFF the input Circuit Breaker of the UPS.

4. Disconnect the AC input power to the UPS.

5. Disconnect the battery string from the UPS.