2.2 Recommended Installation Layout

Verify input (supply) wiring has been run to site in accordance with applicable local and national

electrical codes.

The ACS Series system is heavy equipment. To prevent personal injury or equipment damage, use lifts

and extreme care when handling.

Ventilation and Cooling:

The rectifier/charger is rated to better perform within 18°F (–10°C) and 122°F (+50°C)

temperature range.
To calculate the required air displacement (exchange) volume, please use the following equation:

V = BTU x e (0.125 x H x Tk/To) / (Tr -Tk)

Where:

V = Air flow: [cubic meter/hour]

BTU: Total dissipated heat

Tr: Maximum allowed room temperature [°K] {i.e. 50°C = 323°K]

Tk= Temperature of input cooling air

To= 273 °K H = Altitude [km]

For adequate ventilation and safe access, verify the following minimum clearances around the charger:

3 in. (10 cm) on the sides and top of the unit.
7 in. (18 cm) in back of the unit.
3 feet (1 meter) in front of the unit.
Should seismic conditions require a more secure installation the unit may be bolted to the floor.

Four (4) holes are provided for this purpose.

23.6”/600mm

21.1”/536mm

24.6”/625mm

23”/584mm

Fig. 2-1, Cabinet Footprint with dimensions