2 rectifier operational status, Ac on, Dc on – Alpha Technologies ACS HP Series User Manual

Page 18: Alarm, Fig. 3-1, rectifier leds 3.0 operation

Advertising
background image

18

AIP900-0012-B0-001 Rev. A (01/2012)

For detailed installation, operation and fault diagnosis information, refer to the Cordex 125-

4.4kW Modular Switched Mode Rectifier technical manual (p/n 010-589-B2).

NOTE:

3.2 Rectifier Operational Status

The front panel LEDs provide:

Rectifier Status Summary

Rectifier software upgrade in-progress indication

Locate Module Pattern

Rectifier status summary will show the rectifier alarm status, communication fail status and

rectifier on/off status.

AC ON

The top LED (green) is on when AC is within valid range. The LED will flash (~2Hz) when AC is outside

the normal range - AC voltage is invalid if the AC Mains Low or AC Mains High alarm is active. The

LED turns off when AC has failed.

DC ON

The middle LED (green) is on when the rectifier is delivering power to the load. The LED will flash when

communication is lost. The LED turns off when the rectifier is off; e.g., when commanded via the CXC

Alarm

The bottom LED (red) will flash in the event of an active Module Fail alarm; if the module is unable to

source power as a result of any of the following conditions:

Output fuse blown

AC Mains Input Fail

Module Fail (ramp test fail)

High voltage (OVP) shutdown

Thermal shutdown

Local shutdown

UPF fail

No output power

Fan 1 and 2 fail

The LED will flash (~2Hz) when a minor alarm is detected; if the module’s output capability has been

reduced or a minor component failure has been detected during the following conditions:

VAC meter fail

AC foldback

Remote equalize

Fan (1 or 2) fail

Low output voltage

High output voltage

Current limit (programmable option)

Power limit (programmable option)

High temperature foldback

Temperature sense fail

Soft start operation

Communications lost

The LED remains off in the absence of an alarm. If the unit output is not connected to a battery or parallel

rectifier, the LED will extinguish if no power is present.

1

2

3

2

3

1

Fig. 3-1, Rectifier LEDs

3.0 Operation

Advertising