15.3 TRANSFORMER TESTING

If the transformer is suspected of being faulty, a voltage check of the transformer should be made. The
battery should be disconnected and capacitors in the charger de-energized. With the A1 SCR Driver
board cables disconnected and the secondary wires that go to the SCRs disconnected, the voltages can
be measured. Connect the charger to the nominal AC voltage source of the charger. The voltages on
the transformers should be close to those found in FIGURE 15.3. Use a True RMS meter when taking
the AC voltage measurements.



FIGURE 15.3: TRANSFORMER AC VOLTAGES TABLE

Charger Type

AC Input

Voltage

Secondary

AC Voltage

measured

Wires 5-7 AC

Voltage

measured

24 VDC 6A

120 or 240

64

27

24 VDC 6A

208

64

27

24 VDC 12A

120 or 240

67

27

24 VDC 12A

208

67

27

24 VDC 18A

120 or 240

66

27

24 VDC 18A

208

66

27

24 VDC 20A

120 or 240

66

27

24 VDC 20A

208

66

27

24 VDC 25A

120 or 240

64

26

24 VDC 25A

208

64

26

24 VDC 50A 120

or 240

56

27

24 VDC 50A 208

56

27

48 VDC 6A

120 or 240

131

27

48 VDC 6A

208

131

27

48 VDC 12A

120 or 240

129

27

48 VDC 12A

208

129

27

48 VDC 18A

120 or 240

119

27

48 VDC 18A

208

119

27

48 VDC 20A

120 or 240

119

27

48 VDC 20A

208

119

27

48 VDC 25A

120 or 240

118

28

48 VDC 25A

208

118

28

48 VDC 50A

120 or 240

107

26

48 VDC 50A

208

107

26

130 VDC 6A

120 or 240

317

28

130 VDC 6A 208

317

28

130 VDC 12A

120 or 240

312

27

130 VDC 12A

208

271

27

130 VDC 18A

120 or 240

271

27

130 VDC 18A

208

270

27

130 VDC 20A

120 or 240

271

27

130 VDC 20A

208

270

27

130 VDC 25A

120 or 240

311

27

130 VDC 25A

208

252

29

130 VDC 50A

240

277

28

130 VDC 50A

208

277

28

NOTE: The measured values should be less than 4 volts
higher or lower than the values listed.

Advertising