Charger specifications – Alpha Technologies Spectra Series User Manual

Page 58

Advertising
background image


Preliminary Operating Instructions 58 of 62 AIP SERVICE NUMBER 1-800-863-3364

19. CHARGER SPECIFICATIONS

Specification

Conditions

24 Vdc

48 Vdc

130 Vdc

Vac + 10%, -12%

0 to 100% load

Temp. 32° - 105°F (0 - 40°C)

Output Voltage
Regulation

Freq. 50 - 60 Hz ± 3 Hz

± 0.25%

± 0.25%

Transient
Response

20-100% load charge, with

battery connected

Does not exceed ± 6%. Does not

activate High Voltage Alarm.

Unfiltered on battery

1% V rms

2% V rms

Filtered on battery

30 mV rms

30 mV rms

Filtered off battery

30 mV rms

100 mV rms

Output Ripple
Voltage
(Meets or Exceeds
NEMA PE5-1996
Requirements)

Battery eliminator

30 mV rms

100 mV rms

Current Limit

Adjustable

0 to 110%

Charger Delay

After AC Return

8 Sec. to 60 Mins.

Soft Start

0 to 100% load

Dynamic Depending on Battery Voltage

Float

2.00 V/C to 2.50 V/C

Equalize

2.00 V/C to 2.50 V/C

High DC Voltage alarm

1.00 V/C to 2.70 V/C

Low DC Voltage alarm

1.00 V/C to 2.50 V/C

Voltage
Adjustment Range

End of Discharge Voltage

alarm

1.00 V/C to 2.00 V/C

Voltmeter Range,
Vdc

0.40 V/C to 3.00 V/C

Ammeter Range,
Adc

All ratings

0 to 120%

Reverse Current
From Battery

AC input power failure; no

options installed

Less than 90 mA

Audible Noise

Average for 4 sides, 5 feet

from charger

Less than 62 dB (A)

Cooling Natural

Convection

Ambient
Temperature

Operating

32° - 105°F (0 - 40°C)

Elevation

Without Derating

1000 m (3000 ft)

Relative Humidity

Non-condensing

0 – 95%

Max. Switching Voltage

150 VDC, 125 VAC

Max. Switching Power

30 WDC, 60 VA AC

Max. Switching Current

2.0 A

Alarm Relay
Contact Rating

Max. Carry Current

2.0 A