Ac electrical supply, 1 ac input connections, Figure 6.1-1: ratings and breakers table – Alpha Technologies Spectra Series User Manual

Page 13

Advertising
background image


Preliminary Operating Instructions 13 of 62 AIP SERVICE NUMBER 1-800-863-3364

6. AC ELECTRICAL SUPPLY

The charger must be connected to a single-phase power source. All models can operate on an AC power
source input frequency of 50 or 60 + 3% Hertz. Check the label on the front of the charger or contact the
manufacturer for proper AC power source. The AC input voltage is pre-wired at the factory to 120, 208 or 240
(+10% / -12%) VAC and should not be changed.

NOTE: Field alteration of input voltage voids the charger’s UL Listing.

The AC input wiring must be sized and installed in compliance with the National Electric Code and all
applicable state and local codes and requirements. A qualified electrician must install the AC input wiring
system.

CAUTION: TO REDUCE THE RISK OF FIRE, USE ONLY CIRCUITS PROVIDED WITH BRANCH

CIRCUIT PROTECTION IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE, ANSI/NFPA 70.

6.1 AC INPUT CONNECTIONS

The standard charger is shipped with conduit knockouts and no AC power supply cord. A qualified
electrician must perform this AC input wiring work.

FIGURE 6.1-1: RATINGS AND BREAKERS TABLE

DC Output

AC Input

Rated

DC

Volts

Rated

DC

Amps

Rms.

DC

Amps

DC

Circuit

Breaker

Amps

Optional

Cable

Size

AWG

Rated

AC Input

Volts

Rated

AC

Amps

AC

Frequency

Hz

AC

Circuit

Breaker

Amps

24

6

10

15

14

120 only

5

60 or 50

10

24

6

10

15

14

208 only

3

60 or 50

10

24

6

10

15

14

240 only

3

60 or 50

10

24

12

20

30

12

120 only

7

60 or 50

10

24

12

20

30

12

208 only

5

60 or 50

10

24

12

20

30

12

240 only

5

60 or 50

10

24

18

35

40

8

120 only

10

60 or 50

15

24

18

35

40

8

208 only

6

60 or 50

10

24

18

35

40

8

240 only

6

60 or 50

10

24

20

35

40

8

120 only

12

60 or 50

15

24

20

35

40

8

208 only

7

60 or 50

10

24

20

35

40

8

240 only

7

60 or 50

10

24

25

40

60

8

120 only

14

60 or 50

20

24

25

40

60

8

208 only

8

60 or 50

10

24

25

40

60

8

240 only

8

60 or 50

10

24

50

80

90

6

120 only

24

60 or 50

30

24

50

80

90

6

208 only

15

60 or 50

20

24

50

80

90

6

240 only

15

60 or 50

20

Notes: All input AC circuit breakers are of the “high inrush” type to prevent nuisance tripping during power-up.