Figure 5.2-3: wall anchor design loads table, 3 rack mounting, Figure 5.3: attaching rack-mounting brackets – Alpha Technologies Spectra Series User Manual

Page 12

Advertising
background image


Preliminary Operating Instructions 12 of 62 AIP SERVICE NUMBER 1-800-863-3364

FIGURE 5.2-3: WALL ANCHOR DESIGN LOADS TABLE

Charger Type

Enclosure size

Charger weight

lbs. (Kg)

Design load

lbs. (Kg)

24VDC 6A

S1

70 (32)

350 (159)

24VDC 12A

S1

75 (34)

375 (170)

24VDC 18A

S1

85 (39)

425 (193)

24VDC 20A

S1

85 (39)

425 (193)

24VDC 25A

S1

90 (41)

450 (204)

24VDC 50A

S3

190 (86)

950 (432)

48VDC 6A

S1

75 (34)

375 (170)

48VDC 12A

S1

90 (41)

450 (204)

48VDC 18A

S1

110 (50)

550 (249)

48VDC 20A

S1

110 (50)

550 (249)

48VDC 25A

S1

115 (52)

575 (261)

48VDC 50A

S3

222 (100)

1110 (500)

130VDC 6A

S1

100 (45)

500 (227)

130VDC 12A

S1

130 (59)

650 (295)

130VDC 18A

S2

175 (79)

875 (397)

130VDC 20A

S2

175 (79)

875 (397)

130VDC 25A

S2

190 (86)

950 (432)

130VDC 50A

S3

340 (154)

1700 (771)

FIGURE 5.2-3 shows the weight that the set of mounting bolts and their anchoring structure must
withstand for the various charger types. The “DESIGN LOAD” shows the “CHARGER WEIGHT” times a
safety factor of five (5). Be certain that both the mounting structure and the bolts will, at a minimum,
support the “DESIGN LOAD”. Drywall or plaster will not be strong enough on its own, without proper
structural reinforcement.

5.3 RACK MOUNTING

The S1, S2 and S3 cabinets can be mounted to a standard EIA 19” (483mm) rack system using the
fasteners provided by the rack manufacturer. The rear mounting flanges are configured for an EIA 19”
(483mm) rack for a forward mounting arrangement. For a recessed mounting arrangement, optional
mounting brackets can be attached to the charger sides to fit either an EIA 19” (483mm) or a 23”
(584mm) rack. See FIGURE 5.3.

FIGURE 5.3: ATTACHING RACK-MOUNTING BRACKETS

CAUTION: TO ENSURE THE STRUCTURAL INTEGRITY OF THE RACK MOUNTING

BRACKETS, USE THE SIXTEEN #10 SELF-THREADING SCREWS PROVIDED IN THE KIT. USE
EIGHT SCREWS PER BRACKET AND TIGHTEN THEM UNTIL SNUG. DO NOT STRIP THE
THREADS.

Advertising