Preliminary Operating Instructions 14 of 62 AIP SERVICE NUMBER 1-800-863-3364

FIGURE 6.1-1: RATINGS AND BREAKERS TABLE

DC output

AC input

Rated

DC

Volts

Rated

DC

Amps

Rms.

DC

Amps

DC

Circuit

Breaker

Amps

Optional

Cable

Size

AWG

Rated

AC Input

Volts

Rated

AC

Amps

AC

Frequency

Hz

AC Circuit

Breaker

Amps

48 6 10 15 14

120

only

7

60 or 50

10

48

6

10

15

14

208 only

5

60 or 50

10

48

6

10

15

14

240 only

5

60 or 50

10

48

12

20

30

12

120 only

14

60 or 50

20

48

12

20

30

12

208 only

8

60 or 50

15

48

12

20

30

12

240 only

7

60 or 50

10

48

18

35

50

8

120 only

17

60 or 50

30

48

18

35

50

8

208 only

11

60 or 50

15

48

18

35

50

8

240 only

10

60 or 50

15

48

20

35

50

8

120 only

18

60 or 50

30

48

20

35

50

8

208 only

12

60 or 50

15

48 20 35 50 8

240

only

10

60 or 50

15

48

25

40

60

8

120 only

28

60 or 50

30

48

25

40

60

8

208 only

14

60 or 50

20

48

25

40

60

8

240 only

13

60 or 50

20

48 50 80 90 6

120

only

45

60

or

50 60

48 50 80 90 6

208

only

25

60

or

50 40

48 50 80 90 6

240

only

23

60

or

50 40

130

6

10

15

14

120 only

14

60 or 50

20

130

6

10

15

14

208 only

9

60 or 50

15

130

6

10

15

14

240 only

8

60 or 50

15

130 12 20 25 12

120

only

27

60

or

50 40

130 12 20 25 12

208

only

17

60 or 50

30

130 12 20 25 12

240

only

15

60

or

50 25

130

18

35

40

8

120 only

45

60 or 50

60

130

18

35

40

8

208 only

24

60 or 50

40

130

18

35

40

8

240 only

21

60 or 50

30

130

20

35

40

8

120 only

45

60 or 50

60

130

20

35

40

8

208 only

24

60 or 50

40

130

20

35

40

8

240 only

22

60 or 50

30

130

25

40

60

8

120 only

63

60 or 50

70

130

25

40

60

8

208 only

32

60 or 50

40

130

25

40

60

8

240 only

32

60 or 50

40

130 50 80 90 4

208

only

70

60 or 50

90

130

50

80

90

4

240 only

60

60 or 50

70

Notes: All input AC circuit breakers are of the “high inrush” type to prevent nuisance tripping during power-up.

Wiring and connections must meet the requirements of the National Electric Code, state and local codes
and requirements, and the requirements in this manual.

To connect the input AC voltage, route the AC conduit through the appropriate knockout hole. See
SECTION 6.3. Route the AC wiring to terminal lugs AC1 and AC2 located above the AC breaker as
shown in FIGURE 6.1-2. For proper connection, torque the AC1 and AC2 terminal strip screws to
18 inch pounds (2Nm), and the ground lug screw to 35 inch pounds (4Nm), see FIGURES 6.1-2
and 6.1-3.