Tech menus – Alpha Technologies Spectra Series User Manual

Page 38

Advertising
background image


Preliminary Operating Instructions 38 of 62 AIP SERVICE NUMBER 1-800-863-3364

AC Low Armed or Disarmed ---------------------------------------“AC Lo Armed

→”

---------------------------------------------------------------------------“AC

Lo

Disarmed

→”

DC High Armed or Disarmed --------------------------------------“DC Hi Armed

→”

---------------------------------------------------------------------------“DC

Hi

Disarmed

→”

DC Low Armed or Disarmed ---------------------------------------“DC Lo Armed

→”

---------------------------------------------------------------------------“DC

Lo

Disarmed

→”

DC Failure Armed or Disarmed------------------------------------“DCFail Armed

→”

---------------------------------------------------------------------------“DCFail

Disarmed

→”

Ground Fault Indicator------------------------------------------------“GFI Armed

→”

Armed or Disarmed ------------------------------------------------“GFI Disarmed

→”

End of Discharge ------------------------------------------------------“EOD Armed

→”

Armed or Disarmed ------------------------------------------------“EOD Disarmed

→”

DC High Volts per Cell Set point -----------------------------------“DC Hi 2.50V/C

→”

DC

High

Set

point

Tenths ----------------------------------------“DC Hi 2.50V/C ”

DC High Set point Hundredths ----------------------------------“DC Hi 2.50V/C ”
High DC Lockout Volts per Cell Set point -----------------------“HiLoc 2.50V/C

→”

High DC Lockout Volts Set point Tenths----------------------“HiLoc 2.50V/C ”
High DC Lockout Volts Set point Hundredths ---------------“HiLoc 2.50V/C “
DC Low Volts per Cell Set point------------------------------------“DC Lo 2.10V/C

→”

DC Low Volts Set point Tenths----------------------------------“DC Lo 2.10V/C ”
DC Low Volts Set point Hundredths ---------------------------“DC Lo 2.10V/C ”
End of Discharge Volts/Cell Set point ----------------------------“EOD 1.70V/C

→”

EOD Volts Set point Tenths --------------------------------------“EOD 1.70V/C ”
EOD Volts Set point Hundredths -------------------------------“EOD 1.70V/C ”
Ground Fault Indicator Set point -----------------------------------“Set GFI Open

→”

GFI Positive Set point ---------------------------------------------“Set GFI Pos

→”

GFI Negative Set point --------------------------------------------“Set GFI Neg

→”

Equalize Settings-----------------------------------------------------------“Eqlz Settings

→”

Equalize

Time--------------------------------------------------------------“Eqlz

Time 1hr

→”

Equalize Hours of Ones ----------------------------------------------“Eqlz Time 2hr ”
Equalize

Hours

of

Tens ----------------------------------------------“Eqlz Time 10hr ”

Equalize Interval ----------------------------------------------------------“Eqlz Int 1Days

→”

Interval Days of Ones ------------------------------------------------“Eqlz Int 1Days ”
Interval Days of Tens -------------------------------------------------“Eqlz Int 11Days ”
Change Equalize Mode
Manual

Start/Manual Stop Eqlz ---------------------------------“Mode: Man/Man

→”

Manual

Start/Automatic Stop Eqlz---------------------------------“Mode: Man/Auto

→”

Automatic Start/Automatic Stop Eqlz -----------------------------“Mode:Auto/Auto

→”

Select Start in Float or Equalize mode ------------------------------“Start in Float

→”

---------------------------------------------------------------------------“Start in Eqlz

→”

Hours Run --------------------------------------------------------------------“Hrs Run 12:34”
Internal Charger Temperature in ºC or °F --------------------------“InTemp 29.00ºC

→”

---------------------------------------------------------------------------“InTemp 84.20°F

→”

Optional External Temperature in ºC or °F ------------------------“ExTemp 29.00ºC

→”

---------------------------------------------------------------------------“ExTemp

84.20°F

→”

Time ---------------------------------------------------------------------------“Mon 06:00:00 AM ”
Set

Time---------------------------------------------------------------------“Time Mon 06:00A

→”

Change

Weekday------------------------------------------------------“TIME:

Mon 06:00A”

Change

Hours ----------------------------------------------------------“TIME: Mon 06:00A”

Change

Mins ------------------------------------------------------------“TIME: Mon 06:00A”

Change

AM/PM --------------------------------------------------------“TIME: Mon 06:00A”

Charger Pause --------------------------------------------------------------“Pause 00 mins

→”

Charger Pause in minutes of Tens --------------------------------“Pause 10 mins “
Charger Pause in minutes of Ones -------------------------------“Pause 10 mins “
Days Till Next Eqlz ---------------------------------------------------------“Next Eqlz 0.00”

TECH MENUS:

Control Board Version----------------------------------------------------“Prod ?? MM/DD/YY”
Optional ALARM I/O Relay Test Start -------------------------------“Relay Start

→”

Optional ALARM I/O Relay Test Stop--------------------------------“Relay Stop

→”

Advertising