Electrical connection, 1 connection with auma plug/socket connector, Electrical connection 11 – AUMA Electric multi-turn actuators SA 07.1 - 48.1_SAR 07.1 - 30.1 NORM User Manual

Page 11: Connection with auma plug/socket connector

Advertising
background image

7.

Electrical connection

Work on the electrical system or equipment must only be carried
out by a skilled electrician themselves or by specially instructed
personnel under the control and supervision of such an electrician
and in accordance with the applicable electrical engineering rules.

7.1

Connection with AUMA plug/socket connector

.

Check whether type of current, supply voltage, and frequency correspond to
motor data (refer to name plate at motor).

.

Loosen bolts (50.01) (figure G-1) and remove plug cover.

.

Loosen screws (51.01) and remove socket carrier (51.0) from plug cover (50.0).

.

Insert cable glands or conduit fittings suitable for connecting cables.
(The enclosure protection stated on the name plate is only ensured if properly
sealed connections are made).

.

Seal cable entries which are not used with sealed threaded plugs.

.

Connect cables according to order-related terminal plan.

.

The terminal plan applicable to the actuator is placed inside the terminal
compartment, the operation instructions are attached to the handwheel in a
weather-proof bag.

A special parking frame (figure G-2) for protection against touching the bare
contacts and against environmental influences is available.

11

Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1

Operation instructions

AUMA NORM

Figure G-1: Connection

50.0

50.01

51.0

51.01

Technical data

Power terminals

1)

Protective earth

Control pins

No. of contacts max.

6 (3 are used)

1 (leading contact)

50 pins/sockets

Marking

U1, V1, W1, U2, V2, W2 according to VDE

1 to 50

Voltage max.

750 V

250 V

Nominal current max.

25 A

16 A

Type of customer connection Screws

Screw for ring lug

Screws

Cross section max.

6 mm

2

(10 AWG)

6 mm

2

(10 AWG)

2.5 mm

2

(12 AWG)

Material: Pin/ socket carrier Polyamide

Polyamide

Polyamide

Contacts

Brass (Ms)

Brass (Ms)

Brass, tin plated or gold plated (option)

1) Suitable for copper wires. For aluminium wires it is necessary to contact AUMA.

From size SA(R) 25.1, the motor connection is realised via a separate terminal board

Table 4: Technical data AUMA plug/socket connectors

Figure G-2: Parking frame (accessory)

Parking frame