14.2 Setting the 3-/4- wire system 4 – 20 mA

.

Connect voltage to electronic position transmitter.

.

Move valve to end position CLOSED.

.

If installed, pull off indicator disc.

.

Connect ammeter for 0 – 20 mA to measuring points (figure P-2).

The circuit (external load) must be connected (max. load R

B

),

or the appropriate connections at the terminals (refer to
terminal plan) must be jumpered, otherwise no value can be
measured.

.

Turn potentiometer (E2) clockwise to the stop.

.

Turn potentiometer (E2) back a little.

.

Turn potentiometer “0“ clockwise until output current starts to increase.

.

Turn back potentiometer “0“ until a residual current of approx. 0.1 mA is reached.

.

Move valve to end position OPEN.

.

Set potentiometer “max.” to end value 16 mA.

.

Move valve to end position CLOSED.

.

Set potentiometer “0“ from 0.1 mA to initial value 4 mA.
This results in a simultaneous shift of the end value by 4 mA, so that the range is
now 4 – 20 mA.

.

Approach both end positions again and check setting. If necessary, correct the
setting.

If the maximum value cannot be reached, the selection of the
reduction gearing must be checked.