Limit and torque switches

Only the same potential can be switched on the two circuits (NC/NO contact) of a
limit or torque switch. If different potentials are to be switched simultaneously,
tandem switches are required.
To ensure correct actuator indications, the leading contacts of the tandem switches
must be used for that purpose and the lagging contacts for motor switching off.

7.10 Fitting of the cover

After connection:

.

Insert the socket carrier (51.0) into the plug cover (50.0) and fasten it with
screws (51.01).

.

Clean sealing faces at the plug cover and the housing.

.

Check whether O-ring is in good condition.

.

Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces.

.

Replace plug cover (50.0) and fasten bolts (50.01) evenly crosswise.

.

Fasten conduit connections with the specified torque to ensure the required
enclosure protection.

13

Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1

Operation instructions

AUMA NORM

Mechanical
lifetime = 2 x 10

6

starts

Type of current

Switch rating I

max

30 V

125 V

250 V

1-phase AC
(ind. load) cos phi = 0,8

5 A

5 A

5 A

DC
(resistive load)

2 A

0,5 A

0.4 A

with gold plated
contacts

min. 5 V, max. 50 V

Current

min. 4 mA, max. 400 mA

Table 5: Technical data for limit and torque switches

NO

NC

NC

NO

RD

BK

RD

BK

BK

2

RD 2

BK

RD

BK

2

RD 2

BK

RD

TSC 1 / TSO 1
LSC 1 / LSO 1

TSC / TSO
LSC / LSO

DSR 1 / DÖL 1
WSR 1 / WÖL 1

DSR / DÖL
WSR / WÖL

Figure G-5

II

Tandem switch

SPDT

DPDT

I

Single switch