7.2

Motor connection for the sizes SA(R) 25.1/SAR 30.1 – SA 48.1.

From the size SA(R) 25.1, the power for the motor is connected to separate
terminals. For this, the cover at the motor connection compartment has to be
removed.
The control contacts are connected to the AUMA plug/socket connector.

Cross section motor terminals:
16 mm² to 70 mm² (6 to 2/0 AWG), depending on the actuator size

7.3

Motor connection for
special motors

For versions with special motors (e.g. DC motors), the connection is
performed directly at the motor (figure G-4).

7.4

Delay time

The delay time is the time from the tripping of the limit or torque switches to the
motor power being removed. To protect the valve and the actuator, we recommend
a delay time < 50 ms. Longer delay times are possible provided the output speed,
output drive type, valve type, and the type of installation are taken into
consideration.
We recommend to switch off the corresponding contactor directly by the limit or
torque switch.

7.5

Controls made by AUMA

In case the required reversing contactors are not to be installed in the control
cabinet, the controls AUMA MATIC or AUMATIC for the sizes SA(R) 07.1 – SA(R)
16.1 can be easily mounted to the actuator at a later date.
For enquiries and more information, please state our commission no. (refer to
actuator name plate).

7.6

Heater

AUMA multi-turn actuators have a heater installed as standard. To prevent
condensation, the heater must be connected.

7.7

Motor protection

In order to protect against overheating and extreme high temperatures at the
actuator, PTC thermistors or thermoswitches are embedded in the motor winding.
The thermoswitch is tripped as soon as the max. permissible winding temperature
has been reached.

Failure to integrate PTC thermistors or thermoswitches into the control circuit voids
the warranty for the motor.

7.8

Remote position transmitter

For the connection of remote position transmitters (potentiometer, RWG) shielded
cables must be used.

12

Multi-turn actuators SA 07.1 – SA 48.1 / SAR 07.1 – SAR 30.1
AUMA NORM

Operation instructions

Figure G-4: Connection special motor

Figure G-3: Connection to SA(R) 25.1

Cover motor connection compartment

AUMA plug/socket connector