Electricalinstallation

9.2.1. Electrical installation with cable gland

Procedure:

The screw-type terminals can be accessed by unscrewing the
body casing (stainless steel).

Push the cables through the cable gland.

Connect the wires.

1

2

2)

3

2)

4

5

6

7

Fig. 9:

Screw-type terminals

Terminal

Configuration

1

Binary input +

2

2)

Analogue position feedback +

3

2)

Analogue position feedback GND

4

Set-point value +

(0/4 - 20 mA)

5

Set-point value GND

6

Supply voltage +

24 V DC

7

Supply voltage

GND

Tab. 3: Electrical installation with cable gland

2)

only optional

Seal
Body casing

Body casing

Fig. 10: Position of the seal in the body casing

Check that the seal is correctly positioned in the body casing.

NOTE!

Damage or malfunction due to penetration of dirt and humidity!
To ensure protection class IP65 / IP67:
• Tighten the union nut on the cable gland according to the cable

size or dummy plugs used (approx. 1.5 Nm).

• Screw the body casing in all the way.

Tighten union nut on the cable gland (torque approx. 1.5 Nm).

Close the device (assembly tool: 674077

3)

).

When the supply voltage is applied, the positioner is operating.

Actuate the automatic adjustment of the positioner, as described
in the chapter entitled “10.2. Automatic adjustment X.TUNE”.

3)

The assembly tool (674077) is available from your Bürkert sales office.

english

Type 8694