Start-up

NOTE!

Avoid maladjustment of the controller due to an incorrect
pilot pressure or applied operating medium pressure!
• Run

X.TUNE whenever the pilot pressure (= pneumatic auxil-

iary energy) is available during subsequent operation.

• Run the

X.TUNE function preferably without operating medium

pressure to exclude interference caused by flow forces.

To run

X.TUNE, the positioner must be in the AUTOMATIC

operating status (DIP switch 4 = OFF).

Screw off the transparent cap of the positioner to operate the
keys and DIP switches.

1 2 3 4

ON DIP

Communications
interface
LED 1
LED 2
DIP Switches

Key 1

Key 2

Fig. 14: Automatic adjustment X.TUNE

Start the

X.TUNE by pressing key 1

6)

for 5 s.

While the

X.TUNE is running, LED 1 flashes quickly (green).

When the automatic adjustment is complete, LED 1 flashes slowly
(green)

7)

.

The changes are automatically transferred to the memory (EEPROM)
provided the

X.TUNE function is successful.

NOTE!

Damage or malfunction due to penetration of dirt and humidity!
• To observe protection class IP65 / IP67, screw the transparent

cap in all the way.

Close the device (assembly tool: 674077

8)

).

Important:
When the Teach function is activated the actuator cannot
be actuated via the AS Interface.

6)

The X.TUNE can also be started via communications software.

7)

If a fault occurs, LED 1 is lit red.

8)

The assembly tool (674077) is available from your Bürkert sales office.