19

Start-up

Bus connection without external / with external supply voltage

Pin

Designation

Configuration

1

Bus +

AS Interface bus line +

2

NC or GND
(optional)

not used or external supply voltage –
(optional)

3

Bus –

AS Interface bus line –

4

NC or 24 V +
(optional)

not used or external supply voltage +
(optional)

Tab. 5: Pin assignment of circular plug-in connector for AS Interface

When the supply voltage is applied, the positioner is operating.

Actuate the automatic adjustment of the positioner, as described
in the chapter entitled “10.2. Automatic adjustment X.TUNE”.

9.3.2. Programming data AS Interface

Version Profile S-7.3.4

Version Profile S-7.A.5

I/O con-
figuration

7 hex

7 hex

ID code

3 hex (analog profile)

A hex

Extended
ID code 1

F hex (Default value, can
be changed by the user)

F hex

Extended
ID code 2

4 hex

5 hex

Profile

S-7.3.4

S-7.A.5

Tab. 6: Programming data

10. START-UP

10.1. Safety instructions

WARNING!

Risk of injury from improper operation!
Improper operation may result in injuries as well as damage to the
device and the area around it.
• Before start-up, ensure that the operating personnel are familiar

with and completely understand the contents of the operating

instructions.

• Observe the safety instructions and intended use.
• Only adequately trained personnel may operate the equipment/

the device.

10.2. Automatic adjustment X.TUNE

To adjust the positioner to local conditions, the

X.TUNE

function must be run following installation.

WARNING!

Danger due to the valve position changing when the X.TUNE
function is running!
When the

X.TUNE is running under operating pressure, there is an

acute risk of injury
• Never run

X.TUNE while a process is running!

• Take appropriate measures to prevent the equipment from being

accidentally actuated!

english

Type 8694