Technicaldata

6.7. Electrical data

Connections

Circular plug-in connector
(M12 x 1, 8-pole)

Pilot valve
Supply voltage

24 V DC ± 10%

- max. residual ripple 10 %

Power input

≤ 3.5 W

Input resistance

for set-point value signal

180 Ω at 0/4 – 20 mA /
12 bit resolution

Protection class

3 in accordance with VDE 0580

Analogue position feedback
max. load for current output
0/4 – 20 mA

560 Ω

Binary input

0 – 5 V = log “0”,
12 – 30 V = log “1”
inverted input in reverse order

Communications
interface

Direct connection to PC via USB
adapter with integrated interface
driver, communication with com-
munications software based on
FDT/DTM technology, see “Tab. 11:
Accessories”

.

6.8. Factory settings of the positioner

Functions can be activated via DIP switches:

Function

Parameter

Value

CUTOFF

Sealing function below
Sealing function above

2 %
98 %

CHARACT

Select characteristic

FREE

2)

DIR.CMD

Effective direction set-point
value

rise

Tab. 2: Factory settings - functions

Additional functions are described in the operating instruc-
tions Type 8696 and in the communication software.
These instructions can be found on the Internet at

www.burkert.com

and are also available on CD which can be ordered by
quoting identification number 804625.

2)

without change to the settings via the communications software
a linear characteristic is stored in FREE.