Start-up – Burkert Type 8696 User Manual

Page 16

Advertising
background image

16

Start-up

9.2. Electrical installation with circular

plug-in connector

Connect the positioner according to the table.

6

1

7

5

4

3

2

8

Fig. 8:

Circular plug M12 x 1, 8-pole

Pin

Wire color

3)

Configuration

1

white

Set-point value

+

(0/4 ... 20 mA)

2

brown

Set-point value

GND

3

green

Supply voltage

GND

4

yellow

Supply voltage

+

24 V DC

5

grey

Binary input

+

6

pink

Binary input

GND

7

blue

Analogue position feedback

GND

8

red

Analogue position feedback

+

Tab. 3: Connection with circular plug-in connector

When the supply voltage is applied, the positioner is operating.

Actuate the automatic adjustment of the positioner, as described
in the chapter entitled “10.2. Automatic adjustment X.TUNE”.

3)

The indicated colors refer to the connecting cable available as an
accessory (919061).

10. START-UP

10.1. Safety instructions

WARNING!

Risk of injury from improper operation!
Improper operation may result in injuries as well as damage to the
device and the area around it.
• Before start-up, ensure that the operating personnel are familiar

with and completely understand the contents of the operating

instructions.

• Observe the safety instructions and intended use.
• Only adequately trained personnel may operate the equipment/

the device.

10.2. Automatic adjustment X.TUNE

To adjust the positioner to local conditions, the

X.TUNE

function must be run following installation.

WARNING!

While the X.TUNE function is running, the valve automatically
moves from its current position!
• Never run

X.TUNE while a process is running!

• Take appropriate measures to prevent the equipment from being

accidentally actuated!

english

Type 8696

Advertising