Controlanddisplayelements

7.6.

Error messages

7.6.1.

Error messages in MANUAL and AUTOMATIC operating
statuses

Display

Cause of fault

Remedial action

LED 1 (red)
on

Checksum error in data memory
→ Data memory defective
→ The device automatically switches to an older

(possibly not current) data record.

Not possible, device defective

Table 11:

Error messages in the operating statuses

7.6.2.

Error messages while the X.TUNE function is running

Display

Cause of fault

Remedial action

LED 1 (red)
on

No compressed air connected

Connect compressed air

Compressed air failure while the

X.TUNE

function was running

Check compressed air supply

Actuator or control system deaeration side
leaking

Not possible, device defective

Control system aeration side leaking

Not possible, device defective

Table 12:

Error messages for the X.TUNE function