21

TechnicalData

6.5.

electrical data

6.5.1.

electronic base module me02, me03 / 2-fold monostable

technical data

me02 / 2-fold

monostable

me03 / 2-fold

monostable

Dimensions WxHxD

22 x 70.5 x 52 mm

33 x 93 x 60 mm

Weight

35 g

47 g

Storage temperature

-20 ... +60° C

-20 ... +60° C

Nominal load voltage

DC 24 V

DC 24 V

Number of valve outputs

2

2

Power consumption per valve location during
switching

43 mA

85 mA

Power consumption per valve location after
approx. 120 ms (for ME03 approx. 400 ms)

28 mA

52 mA

Power consumption from the backplane bus

max. 10 mA

max. 10 mA

Display of the valve status

1 yellow LED per valve

location

1 yellow LED per valve

location

Power loss of the module at the point of switching

2 W

4 W

Power loss of the module 100 ms after the switching
process (2 x 0.25 W power loss on resistors,
2 x 0.25 W on valve coils)

1 W

-

Power loss of the module 400 ms after the switching
process (2 x 0.5 W power loss on resistors,
2 x 0.5 W on valve coils)

-

2 W