61

Maintenance,Troubleshooting

9.

mainTenance, TrOuBleshOOTing

9.1.

safety instructions

DANgEr!

risk of injury from high pressure in the equipment!

• Before dismounting pneumatic lines and valves, turn off the pressure and vent the lines.

risk of injury due to electrical shock!

• Before reaching into the device or the equipment,

switch off the power supply and secure to prevent

reactivation!

• Observe applicable accident prevention and safety regulations for electrical equipment!

WArNINg!

risk of injury from improper maintenance!

• Maintenance may be carried out by authorized technicians only and with the appropriate tools!

risk of injury from unintentional activation of the system and an uncontrolled restart!

• Secure system from unintentional activation.

• Following maintenance, ensure a controlled restart.

9.2.

Troubleshooting

malfunction

possible cause

remedial action

Valves do not switch

No or inadequate operating voltage Check the electrical connection

Ensure the operating voltage according to type
plate.

Manual actuation not in neutral
position

Move manual actuation to zero position

Inadequate or no pressure supply

Design the pressure supply with the largest
possible volume (even for upstream devices
such as pressure controllers, maintenance units,
shut-off valves, etc.)
minimum operating pressure ≥ 2.5 bar