English, 4 parameters – Burkert Type TAT002 User Manual

Page 10

Advertising
background image

8 - 0911

english

2.4

Parameters

Control

Hy1

Hysteresis 1

Switch hysteresis of Set-value 1 with
positive or negative values. The default
range is dependent on the input type.
The parameter may not be entered as
zero.

LS1

Lowest set-value setting

Set-value limits for operator

US1

Highest set-value setting

Set-value limits for operator

S1C

control effect

in = inverse (heating, humidification)
dir = direct (cooling, dehumidification)

AC

Minimum switch duration

0...250 sec relay switch-off duration

on

Minimum switch-on period

0...250 sec relay switch-on period

ono

Minimum delay

0...120 min; minimum delay between two
activations of the control relay.

Alarms

ALC

Configuration

rE = relative to the set-value (in Kelvin)

Temperature alarm

Ab = absolute values (in °C)

ALL

Low temperature alarm

If SET - ALL is undershot,
a low temperature alarm will be triggered
after the delay time ALd.

ALU

Over-temperature alarm

If SET + ALU exceeded, a high
temperature alarm will be triggered after
delay time ALd.

ALd

Alarm delay

0...999 min; Minimum time in which the

at temperature

conditions for an alarm situation

Overshoot/Undershoot

must be present.

Sensor

Lower limit

Upper limit

NTC

-40°C

110°C

PTC

-50°C

150°C

Pt100

-200°C

600°C

TcK

0°C

1300°C

TcJ

0°C

600°C

TcS

0°C

1400°C

MEASUREMENT LIMITS FOR THE SENSOR TYPES