English – Burkert Type TAT002 User Manual

Page 12

Advertising
background image

10 - 0911

english

NOTE

You can access hidden paramaters by holding down the keys
SET + for 3 sec in the programming level HY. The message Pr2
appears.

Digital inputs

HES

Temperature increase/

Set-value is increased/lowered by HES

Reduction

during the energy saving phase.

i1F

Function of the digital

EAL = external alarm; OFF = unused;

Input

bAL = serious external alarm;
Es = Energy saving mode Start/Stop;
onF = switch the device ON/OFF
externally;
C-H = reverse the control effect

i1P

Polarity of the digital

CL: active with closed contact

input

OP: active with opened contact

did

Alarm delay time

For i1F = EAL or i1F = bAL.

of the digital input

The corresponding alarm

(1...120 min)

display or message then takes place

Miscellaneous

Adr

Serial address RS485

Address for XJ500 recording

(1...247)

system. Identifies the device if it
is linked into a ModBUS-compatible
system.

OnF

Set device to STAND-BY

no = not possible via keyboard
yes = STAND-BY can be activated by
holding down the SET button of at least
4 sec. During a STAND-BY, OFF is
displayed.

Ptb

Number of the parameter-

only read-out value

table

rEL

Version

only read-out value

Pr2

Display of the parameters in

display only

Level Pr2