English – Burkert Type TAT002 User Manual

Page 17

Advertising
background image

0911 - 15

english

PIN ASSIGNMENT

12 V AC/DC or 24 V AC/DC

Standard signal input: 0...1 V; 0...10 V = 7(+), 9(-)

4...20 mA = 7(+), 9(-)

Thermoelement J, K, S = 7(+) - 9(-)
sensor: Pt100 = 7 - 9(8)
voltage supply: 24 V AC/DC = 11 - 12

230 V AC

Standard signal input: 0...1 V; 0...10 V = 9(+), 11(-)

4...20 mA = 9(+), 11(-)

Thermoelement J, K, S = 9(+) - 11(-)
sensor: Pt100 = 9 - 11(10)
voltage supply: 230 V AC = 7 - 8

operating
contacts
(1, 2, 3)

alarm
contacts
(4, 5, 6)

operating
contacts
(1, 2, 3)

alarm
contacts
(4, 5, 6)