English – Burkert Type TAT002 User Manual

Page 11

Advertising
background image

0911 - 9

english

Alarms

ALH

Hysteresis for the

Automatic alarm acknowledgement:

Limit value alarms

With high alarm undershot by

ALL and ALU

ALU - ALH and with low alarm with
under shooting of ALL + ALH
(0.1 K...upper measurement range)

dAO

Alarm delay at

0...23.5 hours; suppression of

with Mains ON

Alarms after commissioning.

S01

Status of the control relay

oFF = opened

with sensor fault

on = closed

tbA

Status of the control relay

oFF = Relay deactivated

after acknowledgement (by

on = Relay activated

(any button) in an
alarm situation

AS

Configuration of the alarm

cL = Terminal 4-5 closed

relay at an alarm

oP = Terminal 4-6 closed

Measured value display

LCI

Lower analog

Lower display value for current input

Display value

4 mA or with voltage input 1 V

(-1999...1999)

or 10 V (only for inputs 4-20
mA, 0-1V, 0-10 V)

UCI

Upper analog

Upper display value for current input

Display value

20 mA or for voltage input 1 V or 10 V

(-1999...1999)

(only for the 4-20 mA, 0-1V, 0-10 V
inputs)

OPb

calibration of the sensor

regardless of the measurement range

rES

Resolution

in = only whole numbers
dE = also tenths
ce = hundreths

UdM

Units

Display of the units directly in the
illuminated display. Regardless of which
controller type is being used:
see

General description

PbC

Type of sensor

Type of inout

Temperature sensor U):

J = Thermoelement „J“; Pt = Pt100;
C = Thermoelement „K“; Ptc = PTC;
S = Thermoelement „S“; ntc = NTC

Current / voltage input

cur = 4...20 mA; 0-1 = 0...1 V;

(AU)

10 = 0...10 V

P3F

Third terminal of a

(if present)

Pt100 sensor

no = Pt100 2-wire wired
yES = Pt100 3-wire wired

Advertising