English – Burkert Type 8625 User Manual

Page 32

Advertising
background image

30 - 8625-2 Standard

english

From K

crit

and T

crit

, the controller parameters can then be calculated using the

following table.

Parameter setting according to Ziegler and Nichols:

The adjustment rules of Ziegler and Nichols have been determined for P members
with first order time increase and dead time. However, they apply only for
controllers with disturbance behaviour and not for those with command behaviour.

Controller type

Parameter setting

P

K

p

= 0,5 K

krit

-

PI

K

p

= 0,45 K

krit

T

N

= 0,85 T

krit

Advertising