8625-2 Standard - 31

english

6.6.6

INV - heating (non-inverted control)/cooling

(inverted control)

Heating (non-inverted control):

NO

Output signal y of the PI controller
increases with increasing positive
control difference x

d

= w-x.

Cooling (inverted control):

YES

Output signal Y of the PI controller
increases with increasing negative
control difference x

d

= w-x.

Example of applications:

Heating: : In the case of „heating“, a warmer fluid is added to a fluid flow by
means of a proportional valve. The temperature of the mixed fluid is measured
and the addition of the warmer fluid controlled.

Cooling: In the case of „cooling“, a cooler fluid is added to a fluid flow by
means of a proportional valve. The temperature of the mixed fluid is measured
and the addition of the cooler fluid controlled.

Î Via this function you set the sense of action between the input signal and

the setpoint of the valve (factory setting: NO).

non-inverted control

y = K

p

(x

d

+ T

A

/T

N

∑ x

d

)

inverted control

y = - K

P

(x

d

+ T

A

/T

N

∑ x

d

)

Fig.: Heating (non-inverted control)/cooling (inverted control)