7

ERROR MESSAGES

Display

Cause

Remedy

ERR0

Sensor breakage at PT 100

Check sensor if applicable or its

sensor input or current

connection to controller.

temperature lies outside range
(- 50 °C ... 150 °C,
58 °F ... 302 °F)

ERR1

Standard signal of external

Check standard signal.

setpoint lies outside range
(4 - 20 mA, 0 - 10 V)

ERR2

Controller output to proportional

Increase the pressure in order to

valve is greater than 95%.

reach the required setpoint with the
proportional valve selected.

ERR9

Only in mode "external setpoint" Set the values correctly
with

EXLO

≥ EXHI

(see 6.6.3).

Set the lower limit for valve drive
correctly
(see 6.6.8

VALV).

Actual value too great (can no
longer be compensated) or in
manual mode, the valve cannot
be closed.