8625-2 Standard - 33

english

6.6.8

VALV - adaptation of controller output signal

In the menu item

VALV, the

actual value is displayed.

Display of pulse-duty factor of valve

Î With this key, the pulse-duty factor of the

proportional valve is increased, i.e. it opens
up to a max. of 100%.

Î With this key, the pulse-duty factor of the

proportional valve is decreased.

As soon as the controller output is changed by pressing
the

or

key, the display changes automatically to

controller output. On releasing the key, the actual value
is again displayed.

In this menu item, the controller output can be adapted optimally to the working
range of the actuator currently covered in the application. The proportional valve
is driven by a pulse width modulated (PWM) signal from the controller. Opening of
the valve does not begin at a pulse-duty factor of 0 of the PWM signal, but on
account of the spring force opposing the magnetic force, only at a certain value.
This start of opening depends upon the nominal diameter of the valve, the
admission temperature, and because of temperature dependence of the coil
resistance, also on the coil temperature. The function of the controller can be
optimized by having its output range begin not at 0, but at the start of opening in
the current application.

Display of actual value

Fig.: Adaptation of controller output signal