Technical data

Type 8026- 8036- 8076

6.3.2. General data

Pipe diameter

DN06 to DN400;

For a fitting S020 or S030 the appropriate diameter is determined using the flow rate / DN /
fluid velocity graphs: refer to the operating manuals of the fittings

Type of fitting

• S020 for flowmeter 8026: see related operating manual
• S030 for flowmeter 8036: see related operating manual
• S070 for flowmeter 8076: see related operating manual

fluid temperature

• 8026

• 8036 with fitting S030 in PVC

1)

• 8036 with fitting S030 in PP

1)

• 8036 with fitting S030 in PVDF

1)

, brass

1)

or

stainless steel

1)

• 8076 with fitting S070 in aluminium
• 8076 with fitting S070 in stainless steel

• -15 to +100 °C; Also factor in the fluid temperature/pressure dependency for the 8026

inserted into an S020 fitting: see „Fig. 9“

• 0 to +50 °C; Also factor in the fluid temperature/pressure dependency for the 8036: see

„Fig. 10“

• 0 to +80 °C; Also factor in the fluid temperature/pressure dependency for the 8036: see

„Fig. 10“

• -15 to +80 °C; Also factor in the fluid temperature/pressure dependency for the 8036:

see „Fig. 10“

• max. +80 °C
• max. +100 °C