Burkert Type 8076 User Manual

Page 19

Advertising
background image

19

Installation and wiring

Type 8026- 8036- 8076

Correct

Incorrect

Fig. 12: Air bubbles within the pipe / Filling of the pipe

Fit the display module (see related operating manual) to para-
meter the device.

Assemble the flowmeter 8036 (see „Fig. 13“) or install the flow-
meter 8026 into the fitting S020 (see „Fig. 14“)

SE36

S030

1

2

3

SE36

S070

1

2

1 : Insert the electronic module in the sensor holder.

2 : Turn the electronic module by a quarter turn.

3 : Secure the electronic module and the S030 fitting only, by
tightening the screw with a suitable tool to a max. tightening
torque of 1 Nm.

Fig. 13: Assembling the SE36 and the fitting S030 or S070

A

B

Check that there is a seal on the fitting
and that it is not damaged. Replace the
seal if necessary.

Place nut A on the fitting and insert
circlip B into the groove.

Carefully insert the device into the
fitting. If assembly is correct, the device
can no longer rotate on itself.

Secure the unit with nut A, tightening
only by hand.

Fig. 14: Installation of flowmeter 8026 into the fitting S020

Set the K factor parameter (see chap. „8.8.8“) or have it deter-
mined through a teach-in procedure.

English

Advertising
This manual is related to the following products: