Burkert Type 8076 User Manual

Page 20

Advertising
background image

20

Installation and wiring

Type 8026- 8036- 8076

7.2.2. recommendations on installing an

8076 on a pipe

Install the fitting S070 on the pipe in such a way that the oval
gear axes are in the horizontal plane, as shown in „Fig. 15“.

Correct

Incorrect

Fig. 15: The oval gear axes must be horizontal (seen from the front)

Fit the display module (see related operating manual) to para-
meter the device.

Assemble flowmeter type 8076 (see „Fig. 13“)

Set the K factor parameter (see chap. „8.8.8“) or have it deter-
mined through a teach-in procedure.

7.3.

Wiring

danger

risk of injury due to electrical voltage.
• Shut down and isolate the electrical power source before

carrying out work on the system.

• Observe all applicable accident protection and safety regula-

tions for electrical equipment.

• Use a high quality electrical power supply (filtered and

regulated).

• Make sure the installation is equipotential. See chap.

„7.3.3“.

• Use a shielded cable.
• Once the device is wired, set the "HWMode" parameter

depending on the wiring carried out, sink/NPN or source/
PNP. See chap. „8.8.3“.

English

Advertising
This manual is related to the following products: