Electrical connections, K factors – Burkert Type 8011 User Manual

Page 20

Advertising
background image

20

Technicaldata

Type 8011

Protection against
polarity reversal

yes

Protection against
spike voltages

yes

Protection against
short circuits

yes, for the pulse outputs

Pulse output

• Version with 1

pulse output

• Version with 2

pulse outputs, NPN
and PNP

transistor

• open collector, 20 mA max., NPN output:

0,2-24 V DC, frequency up to 300 Hz
(frequency = K factor x flow rate).

• open collector, 700 mA max., frequency

up to 300 Hz (frequency = K factor x
flow rate), NPN output: 0,2-36 V DC and
PNP output: Supply voltage

6.3.4. electrical connections

Version

type

With a cable gland

Cable, 1 m

With a fixed connector

Male 5-pin M12 fixed connector

6.3.5. K factors

The K factors have all been determined in the following reference
conditions:
medium = water, water and ambient temperatures 20 °C, min. upstream
and downstream distances respected, appropriate pipe dimensions

Two versions of the S012 in DN15 and DN20 exist, having
different K factors.
Only version 2, identified by the "v2" marking, is available
from March 2012. The "v2" marking can be found:
• on the bottom of the DN15 or DN20 fitting in plastic:

V2

• on the side of the DN15 or DN20 fitting in metal:

V2

English