Installation onto the pipe, Recommandations for installing the 8011 on, The pipe – Burkert Type 8011 User Manual

Page 23

Advertising
background image

23

Installationandwiring

Type 8011

16
15
14
13
12
11
10

9
8
7
6
5
4
3
2
1
0

-20

0

+20

+40 +60

+80 +100 +120

PVDF (PN10)

PP (PN10)

T ( ° C)

P (bar)

PVC + PP

A

PVDF

PVC + PP
(PN10)

Fluid temperature

Metal (PN16)

Fluid pressure

A : range of use for the complete device

Fig. 3: Fluid pressure /temperature dependency curves

7.2.

installation onto the pipe

danger

Danger due to high pressure in the installation.
• Stop the circulation of fluid, cut off the pressure and drain the

pipe before loosening the process connections.

Danger due to high temperatures of the fluid.
• Use safety gloves to handle the device.
• Stop the circulation of fluid and drain the pipe before loosening

the process connections.

Danger due to the nature of the fluid.
• Respect the prevailing regulations on accident prevention and

safety relating to the use of aggressive fluids.

7.2.1. recommandations for installing the

8011 on the pipe

Check that the DN of the fitting is dimensioned to the process
according to the graphs in chap. 7.3.

Install the device on the pipe in such a way that the upstream
and downstream distances are respected according to the
design of the pipes, as per Fig. 4 and the EN ISO 5167-1
standard.

English