Installationandwiring

Type 8011

7.4.

electrical wiring

danger

risk of injury due to electrical discharge
• Shut down and isolate the electrical power source before carry-

ing out work on the system.

• Observe all applicable accident protection and safety regula-

tions for electrical equipment.

note

• Use cables with an operating temperature limit suitable for your

application.

• Protect the power supply of a version with 2 pulse outputs by

means of an 800 mA fuse and a switch.

• Protect the power supply of a version with 1 pulse output by

means of a 50 mA fuse and a switch.

use a high quality electrical power supply (filtered and
regulated).
• Under normal conditions of use, cable with a cross section

of 0.75 mm

2

should be enough to transmit the signal.

• Do not install the cable near high voltage or high frequency

cables.

• If this is unavoidable, keep a minimum distance of 30 cm.

make sure the installation is equipotential (power supply
- 8011):
• Connect the different earth connections of the installation to

one another in order to remove any differences in potential
which may arise between two earth connections.

• Correctly connect the cable shielding to the earth.
• Connect the negative power supply terminal to the earth to

eradicate the effects of common mode currents. If this con-
nection cannot be made directly, a 100 nF/50 V capacitor
can be fitted between the negative power supply terminal
and the earth.

+

-

(*)

(**)

Power supply

8011 with cable gland

+

-

(*)

(**)

Power supply

8011 with m12 fixed

connector

*) If a direct earth connection is not possible, fit a 100 nF/50 V condenser
between the negative power supply terminal and the earth
**) If the cable used is shielded.