Wiring a version with cable gland, English – Burkert Type 8011 User Manual

Page 29

Advertising
background image

29

Installationandwiring

Type 8011

6-36 V DC

+

-

(*)

1

2

3

4

5

blue

grey

white

brown

Load

Power supply

Fig. 11: PNP wiring of the pulse output of a version with M12 fixed

connector

(*) Functional earth; If a direct earth connection is not possible, fit a 100 nF /
50 V capacitor between the negative power supply terminal and the earth.

7.4.3. Wiring a version with cable gland

color of the wire

bn
(brown)

Wh (white) Gn (green) ye (yellow)

Gy
(grey)

Signal on a version
with 1 pulse output

V+

0 V DC

Functional
earth

Not connected NPN

Signal on a version
with 2 pulse
outputs

V+

0 V DC

Functional
earth

PNP

NPN

+

-

(*)

YE GY BN WH GN

Load

grey

brown

white

green

Power supply, 4,5-24 V DC or

6-36 V DC

Fig. 12: NPN wiring of the pulse output of a version with cable

gland

6-36 V DC

+

-

(*)

YE GY BN WH GN

Power supply

Load

brown

grey

white

green

Fig. 13: PNP wiring of the pulse output of a version with cable

gland

(*) Functional earth; If a direct earth connection is not possible, fit a 100 nF /

50 V capacitor between the negative power supply terminal and the earth.

English