english

Installationandwiring

• The power supply must be filtered and regulated.

Make sure the installation is earthed equipotentially
(power supply - 8081).

Connect the different earth connections of the installation to
one another in order to remove any differences in potential
which may arise between the two earth connections.

Connect the cable shielding to the earth. Connect the nega-
tive terminal of the power supply to the earth to remove the
effects of the common mode currents. If this connection can-
not be made directly, a 100 nF/50 V capacitor can be fitted
between the negative terminal of the power supply and the
earth.

+

-

(*)

12-36VDC

(**)

(*) If a direct earthing
connection is not pos-
sible, fit a 100 nF/50 V
capacitor between the
negative terminal of the
power supply and the
earth.

(**) If your cable is
shielded.

notice

When mounting the device on the pipe, the m12 fixed connector
may be damaged.
If the M12 fixed connector is damaged the device cannot be used
anymore.
• Please be careful not to damage the M12 fixed connector when

mounting the device on the pipe.

7.3.

electrical wiring

danger

risk of injury due to electrical discharge
• Before starting work, make sure that you switch off the supply

voltage and secure it to prevent restarting.

• Do not install the cable near high voltage or high frequency ca-

bles.

• If this is unavoidable, keep to a minimum clearance of 30 cm.
• Observe all applicable accident protection and safety guidelines

for electrical equipment