Type 8081

english

Installationandwiring

7.3.3.

connecting the pulse output

The pulse output is connected in NPN mode (default setting on a
version without current output) or in PNP mode (default setting on a
version with current output).

12-36 VDC

+

-

Load

1

2

3

4

5

brown

white

blue

grey

npn connection

12-36 VDC

+

-

Load

1

2

3

4

5

brown

white

blue

grey

pnp connection

7.3.4.

only connecting the current output

The current output, where present, is connected in source mode
(default setting) or in sink mode (on request).

12-36 VDC

+

-

+

-

(*)

4-20 mA

input

1

2

3

4

5

brown

black

blue

grey

Supply

12-36 VDC

+

-

+

-

4-20 mA

input

1

2

3

4

5

brown

black

blue

grey

Supply

(*)

Source mode connection

(default setting)

Sink mode connection

(on request)

(*) If a direct earthing connection is not possible, fit a 100 nF/50 V capaci-
tor between the negative terminal of the power supply and the earth.